Description
The zone monitor unit (CZMU352) connects a zone of suitable Cooper conventional detectors and a separate zone of Cooper conventional callpoints (if required).
Product Description/ Features/ Specifications
An extensive range of interfaces are available to support the Cooper range of control panels, providing solutions for most design requirements.
The zone monitor unit (CZMU352) connects a zone of suitable Cooper conventional detectors and a separate zone of Cooper conventional callpoints (if required).
Features
- Soft addressed
- Integral short circuit isolator
- Single address
- Accepts a zone of Cooper conventional detectors
- Input monitored for open, short circuit and earth contact faults
Benefits
- Quick and simple to install
- No hard addressing required (Plug and play)
- Easy to expand a system using existing wiring
| Code | CZMU352 |
|---|---|
| Description | Zone Monitor Unit |
| Standards | EN54 Pt17 & Pt18 2005 |
| Specification | |
| Operating Voltage | 18V dc to 30V dc |
| Quiescent Current | 2.8mA |
| Alarm Current | 8mA |
| Current with 20 Detectors | 3.4mA |
| Detector Load | 20 detectors per zone (max) |
| Callpoint Load | Unlimited |
| Environmental | |
| Operating Temperature | -10°C to +60°C |
| Humidity (Non Condensing) | 0 to 95% RH |
| Physical | |
| Construction | PC/ABS |
| Dimensions (HxWxD) | 88mm x 147mm x 60mm |
| Weight | 0.23kg |
| Ingress Protection | IP40 |
| Compatibility | |
| Suitable for use with | Cooper Intelligent Addressable Fire Systems |





Reviews
There are no reviews yet.